this post was submitted on 28 Jun 2023
6 points (100.0% liked)

Home Improvement

9090 readers
10 users here now

Home Improvement

founded 2 years ago
MODERATORS
6
submitted 2 years ago* (last edited 2 years ago) by bbbbb to c/homeimprovement
 

Hi folks, I got a heat pump installed at my home and I'm looking to better understand when/how it switches over to backup fuel in the winter.
My unit is the LENNOX ELITE EL18XPV SERIES, which I found heating specs on here
It is installed in conjunction with a heating oil fired boiler and an aqua coil as the backup heat source. When it was installed, I asked, and the installer indicated that the heat pump will switch over to the boiler at about 37F. What I don't fully understand though, is that this unit was billed as a variable speed/inverter, so it seems it should be able to run at lower temperatures than 37. The website above seems to indicate it should produce 31,800 BTU/h at 17F, so can I set the "switch-over" temperature of outside to be lower to use less oil?

you are viewing a single comment's thread
view the rest of the comments
[–] [email protected] 1 points 2 years ago

Idk about that unit specifically, but dual-fuel setups do generally have a way to set their switchover points and contractors are basically always very conservative with where they set them.. I think largely due to them not wanting callbacks on someone's house not heating up fast enough.

You'll have to research your whole setup and figure out where that is.