this post was submitted on 11 Feb 2025
363 points (98.7% liked)

Technology

62064 readers
5111 users here now

This is a most excellent place for technology news and articles.


Our Rules


  1. Follow the lemmy.world rules.
  2. Only tech related content.
  3. Be excellent to each other!
  4. Mod approved content bots can post up to 10 articles per day.
  5. Threads asking for personal tech support may be deleted.
  6. Politics threads may be removed.
  7. No memes allowed as posts, OK to post as comments.
  8. Only approved bots from the list below, to ask if your bot can be added please contact us.
  9. Check for duplicates before posting, duplicates may be removed
  10. Accounts 7 days and younger will have their posts automatically removed.

Approved Bots


founded 2 years ago
MODERATORS
you are viewing a single comment's thread
view the rest of the comments
[–] [email protected] 12 points 7 hours ago* (last edited 3 hours ago) (1 children)

I had no idea that is possible??? Is that special for Germany?

I mean, the regulation seems to be, but there's no fancy tech going on. I'm not an electrician but I think I can explain, as I have recently tried to understand myself. To understand why it's possible it's best to understand why the limit is at 800 W precisely.

So German wall outlets usually have a 16 A fuse and the wiring in the walls is dimensioned to accommodate slightly higher current (I think they are 2.5mm² gauge allowing up to 20 A but don't quote me on that particular part) for safety reasons. I suppose it would be the same or very similar in Denmark, or maybe most of Europe that uses 230V/50Hz AC.

Now, normally, if you have dangerously powerful load that would melt your wires, let's say 5 kW, and you plug it in to an outlet the fuse will just pop and you're safe. If however you have a 2 kW PV system connected to a wall outlet nearby, it would theoretically be possible that your 5 kW load draws 13 A (3 kW) from the mains through the fuse and another 8.7 A (2 kW) from the PV system over the same wire in the wall that is only rated at 20 A but now carries 21.7 A. And the fuse would never pop at 13 A, making it a huge fire hazard. 800 W is basically just what will always comfortably fit into the safety margin of the wiring in German houses. All systems above 800 W need to be hardwired by professionals "behind" the fuse box so that every Amp from your PV goes through a typical 16 A fuse.

still such an 800W system is dirt cheap by comparison

Absolutely. I guess the low threshold for installation allows some kind of mass market economy of scale whereas systems like yours are homeowners' luxury goods.