this post was submitted on 08 Sep 2023
10 points (91.7% liked)
Electricians
491 readers
1 users here now
founded 2 years ago
MODERATORS
you are viewing a single comment's thread
view the rest of the comments
view the rest of the comments
I would not put the AC on a power strip, unless you get a very good power strip.
You should switch the power point to a double gang outlet and stick a power strip on the other plug for your tv and accessories.
You TV may not like inductive loads on the same circuit though so youay lower the life of your tv by doing it.
Thank you for input. I wasnt going to put AC on a power strip, I was going to connect powerstrip on AC terminals and then only TV on a power strip. Well, my plans are changing it seems :)
Also Im not worried about lowering life of TV, but it sounds wrong and I want to avoid everything thats not best practice
Assuming this is a VRF/DX split system you can often hang a small Outside Air Fan off the indoor unit power supply with no problems but anything over an Amp or so you are starting to risk overloading the PCBs in the Condensor unit as they dont have the same current carrying capacity as the cables typically used.
Also not sure about the regulations where you live but you also need to comsider if the GPO for the TV would still be RCD/TCBo protected.
Overall its a bad idea to be putting any non-HVAC related equipment on a circuit designated for an AC unit, this will be confusing and dangerous in regards to power isolation for an electrician doing work in future.
Thank you. 1A is not what I need, but it feels bad after reading this. 1A is only ~220W which seems like dangerously low