this post was submitted on 06 Aug 2023
28 points (100.0% liked)

Electricians

119 readers
1 users here now

For those in the Electrical trade

founded 1 year ago
MODERATORS
 
you are viewing a single comment's thread
view the rest of the comments
[–] [email protected] 11 points 1 year ago (1 children)

Customer reporting pool pump not working. Only getting 1.6V at the receptacle, all others showing 120V. One wire in it, so obviously last one on the circuit. Went to the one before it, found this. All of them backstabbed. Reterminated them all before I left

[–] [email protected] 2 points 1 year ago (1 children)

I'm not an electrician, but I always found the backstab a terrible idea, compared to the screw connectors..

[–] [email protected] 3 points 1 year ago

On receptacles it generally is a bad idea. Things being plugged & unplugged all the time makes for little micro movements of the device that will wear at the thin connection and over time cause a problem. It’s not as big of a problem for switches, not as much movement and beating around