Looking at the diagram, I don't see any issue with the network topology. And the power arrangement also shouldn't be a problem, unless you require the camera/DVR setup to persist during a power cut.
In that scenario, you would have to provide UPS power to all of: the PoE switch, the L3 switch, and the NVR. But if you don't have such a requirement, then I don't see a problem here.