Having gathered more info from your other replies, well, let's say the same but quicker... you know the meme :
'xcept here it'll be GROUND ALL THE THINGS!
The slab, the pipe, the Cat6 conduit, ground it all. If I was in my line of work, there'll be a 6mm² ground wire between both houses.
(Image credit Allie Brosh' excellent "Hyperbole and a half")
The Cat6 is not in conduit - it's direct burial rated cable. It was a bit of an afterthought - I already have a pair of Ubiquiti GigaBeams that are working very well. But, the trench was being dug for the water line so I jumped on Amazon and bought a cheap cable. I ran it my desk as a fly lead for a while to make sure it worked and then dropped it in the trench before it was back filled. If fixing my ground issues doesn't fix the ethernet performance I'll just go back to the GigaBeams.
I might actually be able to achieve that - there's a 4 wire "well pump wire" from my new house back to the well, which is very close to the old house. One of those wires might be a ground and if so, it might make sense to ground it at both ends. I'll look into it.
When I said 6mm² it's because of the distance, you want more copper to get less resistivity between both grounds; your water pump probably run on 1.5 or 2.5² which isn't much - but by all means, please ensure that pump is grounded!
Also because IRL I run elec for open-air festivals & with great responsibility comes great paranoia ;)